Description
WOODWARD
GCP-30
PART NO: 8440-1614
GENSET CONTROL PACKAGE
GCP-3245B/BPQ
REV: J
U OUX: 12/24VDC I OUX,MAX: 1A DC
UMEAS(IEC): 230/400V AC UMEAS,MAX(UL): 300V AC
I 1/GEN: 5A AC I 2/MAINS: 5A AC FN: 50/60HZ
U CONT DIG INPUT: 12/24V DC U CONT,RELAYS: 250V AC
TECHNICAL SPECIFICATIONS:
ACCURACY: CLASS 1
POWER SUPPLY: 12/24 VDC (9.5 TO 32 VDC)
INTRINSIC CONSUMPTION: MAX. 20 W
AMBIENT TEMPERATURE: STORAGE….-30 TO 80°C
OPERATION….-20 TO 70°C
AMBIENT HUMIDITY: 95 %, NON-CONDENSING
DISCRETE INPUTS: GALVANICALLY ISOLATED
INPUT RANGE: RATED VOLTAGE 12 TO 24VDC (6 TO 32 VDC)
INPUT RESISTANCE: APPROX. 6.8 KΩ
RELAY OUTPUTS: POTENTIAL FREE
GENERAL PURPOSE (GP): AC…2.00AAC@250 VAC
DC…2.00ADC@24 VDC
0.18-0.36ADC@125-250 VDC
PILOT DUTY (PD): AC…B300
DC…1.00ADC@24V DC
0.10-0.22ADC@125-250 VDC
GERMANY
The Woodward GCP-30 (8440-1614, REV J) is a genset control package used to control and monitor a generating set within a marine control system. It is identified on the unit as GCP-3245B/BPQ. It measures generator and mains values with 5 A AC current inputs on each side and voltage measurement rated 230/400 V AC (IEC), at 50/60 Hz, to accuracy class 1. The controller runs on 12/24 V DC (9.5 to 32 V DC) with a maximum intrinsic consumption of 20 W. It offers galvanically isolated discrete inputs and potential-free relay outputs. This unit is supplied in used condition.
Key Features
✓ Generator and mains current inputs, 5 A AC each
✓ Voltage measurement 230/400 V AC (IEC), 300 V AC max (UL), 50/60 Hz
✓ Power supply 12/24 V DC (9.5 to 32 V DC), max. 20 W
✓ Galvanically isolated discrete inputs, 12/24 V DC
✓ Potential-free relay outputs, 2.00 A AC at 250 V AC general purpose
Marine Applications
✓ Auxiliary diesel generator control and monitoring
✓ Generator and mains supply monitoring in main switchboards
✓ Emergency generator control panels
✓ Genset control within vessel power management
Technical Support
Prota Marine provides technical support, repair and onboard installation for the Woodward GCP-30 genset control package and the wider marine control system. Fault diagnosis covers its measurement inputs, discrete inputs and relay outputs, and commissioning support is available when the controller is brought back online with the generating set.