Description
NITTAN CO.,LTD.
NFD-68-P
UV TYPE FLAME DETECTOR
INPUT VOLTAGE: 10V TO 30V DC
RATED CURRENT: 165 MA (L-C: 65MA, P+-C: 100MA)
OPERATING CURRENT: 0.15MA MAX
RUSH IN CURRENT: 0.36MA MAX
DETECTION DISTANCE: 25M
DETECTION ANGLE: 100(±50°)
TEST FLAME: NORMAL HEPTANE
33CM x 33CM FUEL PAN
MADE IN JAPAN
Nittan’s NFD-68-P is a UV type flame detector for a marine fire alarm system, watching the protected space for the ultraviolet signature of open flame and triggering an alarm when fire is present. It works from a 10-30 V DC input with a rated current of 165 mA and an operating current of 0.15 mA max. The rated detection distance is 25 m over a 100 (±50°) detection angle, based on a normal heptane test flame in a 33 cm x 33 cm fuel pan. Made in Japan, the detector is in used condition.
Key Features
✓ UV type flame detector
✓ Input voltage 10-30 V DC
✓ Operating current 0.15 mA max, rush in current 0.36 mA max
✓ Detection distance 25 m
✓ Detection angle 100 (±50°)
Marine Applications
✓ Generator set and auxiliary engine flats
✓ Boiler front monitoring
✓ Fuel oil transfer pump rooms
✓ Hydraulic power pack rooms
Technical Support
Prota Marine provides technical support, repair and onboard installation for the UV flame detector and the wider fire alarm system. Our team carries out fault diagnosis on flame detection faults and supports commissioning of the detector on board.