Description
NITTAN CO.,LTD.
NFD-68-P
UV TYPE FLAME DETECTOR
INPUT VOLTAGE: 10V TO 30V DC
RATED CURRENT: 165 MA (L-C: 65MA, P+-C: 100MA)
OPERATING CURRENT: 0.15MA MAX
RUSH IN CURRENT: 0.36MA MAX
DETECTION DISTANCE: 25M
DETECTION ANGLE: 100(±50°)
TEST FLAME: NORMAL HEPTANE
33CM X 33CM FUEL PAN
STB-4
BASE
508696-0066
MADE IN JAPAN
The Nittan NFD-68-P is a UV type flame detector supplied with its STB-4 base (508696-0066). It forms part of a shipboard fire alarm system, where it senses ultraviolet radiation from open flame in the protected space and raises a fire alarm. The detector takes an input voltage of 10-30 V DC and has a rated detection distance of 25 m across a detection angle of 100 (±50°). Its detection performance is referenced to a normal heptane test flame burning in a 33 cm x 33 cm fuel pan. This detector and base set is offered in used condition and was made in Japan.
Key Features
✓ UV type flame detection
✓ Input voltage 10-30 V DC
✓ Rated current 165 mA (L-C 65 mA, P+-C 100 mA)
✓ Detection distance 25 m, detection angle 100 (±50°)
✓ Supplied with STB-4 base 508696-0066
Marine Applications
✓ Flame detection over main engines in the engine room
✓ Purifier and separator room monitoring
✓ Emergency generator room coverage
✓ Incinerator space protection
Technical Support
Prota Marine provides technical support, repair and onboard installation for the UV flame detector and the wider fire alarm system. Our engineers assist with fault diagnosis on detector and base faults and support commissioning once the unit is fitted.