Description
TYCO FIRE & SECURITY GMBH
THORN SECURITY
811FEX
MX ADDRESSABLE IS FLAME DETECTOR
CONFORMS TO: EN 54-10:2002 CLASS 2
516.800.067
THE 811F AND 811FEX POINT TYPE FLAME DETECTORS ARE PART OF THE MX TECHNOLOGY RANGE OF DIGITAL ADDRESSABLE FIRE DETECTORS. MX TECHNOLOGY INCORPORATES HEAT, OPTICAL AND CARBON MONOXIDE DETECTION. THE 811F AND 811FEX FLAME DETECTORS PRESENT A COST-EFFECTIVE SOLUTION TO PROVIDING FALSE ALARM FREE FLAME DETECTION FOR ENCLOSED APPLICATIONS. BOTH THE 811F AND THE 811FEX ARE FULL FEATURED SOLAR BLIND FLAME DETECTORS FOR ENCLOSED USE AND BOAST A HIGH DEGREE OF FALSE ALARM IMMUNITY.
THE STANDARD UNIT IS THE 811F AND IT IS DESIGNED FOR DIRECT CONNECTION TO THE MX DIGITAL LOOP, EMPLOYING THE SAME DETECTOR BASE OR FUNCTIONAL BASE AS OTHER 800 SERIES FIRE DETECTORS. THE 811FEX IS AN INTRINSICALLY SAFE VERSION INTENDED FOR USE IN HAZARDOUS ATMOSPHERES AND MUST BE CONNECTED VIA AN EXI800 INTERFACE AND GALVANIC ISOLATOR. THE DETECTORS ARE DESIGNED TO COMPLY WITH EN 50 014 AND EN50 020 FOR INTRINSICALLY SAFE APPARATUS. THEY ARE CERTIFIED: ATEX CODE: II 1 G CENELEC CODE: EEX IA IIC T4.
MADE IN CZECH REPUBLIC
The Tyco 811FEX (516.800.067) is an MX addressable, intrinsically safe (IS) flame detector for a marine fire alarm system, supplied with its base. It is the IS version of the 811F, a solar blind point flame detector for enclosed areas, intended for hazardous atmospheres and connected to the MX digital loop through an EXI800 interface and galvanic isolator. Its role is to spot flame in spaces where flammable vapours may be present and report it to the fire panel. The unit is certified ATEX II 1 G and EEx ia IIC T4, conforms to EN 54-10:2002 Class 2, and is offered in used condition.
Key Features
✓ MX addressable intrinsically safe flame detector
✓ Solar blind flame detection for enclosed use
✓ Conforms to EN 54-10:2002 Class 2
✓ ATEX II 1 G and CENELEC EEx ia IIC T4
✓ Connects via EXI800 interface and galvanic isolator
Marine Applications
✓ Cargo pump rooms on oil and chemical tankers
✓ Paint lockers and flammable stores
✓ Enclosed hazardous areas on gas carriers
Technical Support
Prota Marine provides technical support, repair and onboard installation for the intrinsically safe flame detector and the wider fire alarm system. We assist with fault diagnosis on the MX loop and the IS interface path, and support commissioning after installation.