Description
CONSILIUM
SALWICO SCI-A
PART NO: 5200120-00A
SHORT CIRCUIT ISOLATOR
ADDRESSABLE IP67
PART NO: 5200120-00A (GB)
1033 694635
THE CONSILIUM SALWICO SCI-A WP 5200120-00A IS A SHORT CIRCUIT ISOLATOR FOR USE IN HARSH OUTDOOR ENVIRONMENTS, AND IS DESIGNED FOR USE IN SALWICO ADDRESSABLE FIRE ALARM SYSTEMS.
THE SELECTED MATERIAL PC/ABS AND THE ENCAPSULATION, WITH INGRESS PROTECTION IP67, MAKES IT VERY SUITABLE FOR HARSH ENVIRONMENT.
THE SCI-A WP IS PLACED BETWEEN THE DETECTOR OR MANUAL CALL POINTS IN THE DETECTOR LOOP. WHEN THERE IS A SHORT CIRCUIT IN THE DETECTOR LOOP, THE SCI-A WP ON EACH SIDE OF THE SHORT CIRCUIT WILL OPEN THE CIRCUIT.
THE ADDRESS OF THE SCI-A WP IS SET BY A DIP SWITCH.
• NOMINAL VOLTAGE: 34VDC
• WORKING VOLTAGE: 20-38 VDC
• IP RATING: IP67
• TEMPERATURE RANGE: -25°C TO +70°C
• RELATIVE HUMIDITY: 0 TO 95% RH
• MATERIAL: PC/ABS
• COLOUR: WHITE
• CERTIFIED ACCORDING TO: 2531, EN 54-17
• SYSTEM/SERIES: CS3000, CS3004, CS4000, SALWICO CARGO, SALWICO CRUISE, SALWICO RO/PAX, SALWICO WORKBOAT, SALWICO YACHT
MADE IN UK
The Consilium Salwico SCI-A (5200120-00A) is an addressable short circuit isolator serving the vessel’s fire alarm system, built for Salwico addressable installations in harsh outdoor locations. Placed between detectors or manual call points in the detector loop, it opens the circuit when a short occurs, with the isolators on either side of the fault both opening. The PC/ABS housing is encapsulated to IP67, nominal voltage is 34 V DC with a 20-38 V DC working range, and the address is set by DIP switch. The unit is offered in new open box condition.
Key Features
✓ 34 V DC nominal, 20-38 V DC working voltage
✓ IP67 encapsulated PC/ABS housing
✓ Opens the loop on each side of a short circuit
✓ Address set by DIP switch
✓ Certified to EN 54-17, rated -25°C to +70°C
Marine Applications
✓ Short circuit isolation in Salwico CS3000, CS3004 and CS4000 detector loops
✓ Outdoor and open-deck sections of addressable fire detection loops
✓ Salwico Cargo, Ro/Pax and Cruise installations
✓ Salwico Workboat and Yacht fire alarm systems
Technical Support